Notice: You are currently viewing the website. View the website instead »

Instrument Current Transformer 2200 Series

Instrument transformer is a general term for voltage transformers and current transformers that are used with electrical instruments. The main purpose of instrument transformers is to extend the measurement range for electrical quantities (voltage, current, power, power factor) on large-current and high-voltage circuits. They serve to convert currents and voltages to levels that are suitable for measurement, and to insulate the instrument, etc. from high-voltage circuitry.

Specifications - Model 2241 00

Conversion Type Current
Current 0.5 ~ 1500 A
Primary 10/15/30/50/100/ 250/300/500/750/1500A
Secondary 5A
Rated Load 15 VA
Relative Error ± 0.2%
Phase Angle ± 10 minutes
Class JIS C 1731 : 1997 Class 0.2
Maximum Circuit Voltage 3450 V
Withstand Voltage 10000 V
Rated Frequency 50 ~ 60 Hz
Approx. External Dimension 318 x 246 x 128 mm
Approx. External Weight 9 kg

Features

  • Precision conversion of electrical quantities on AC large-current or high-voltage circuits
  • Secondary circuit is isolated from primary circuit.
  • Capable of wide-range measurement using numerous ranges

 

Specifications - Model 2242 00

Conversion Type Current
Current 0.5 ~ 1500 A
Primary 10/15/30/50/100/ 250/300/500/750/1500A
Secondary 5A
Rated Load 15 VA
Relative Error ± 0.2%
Phase Angle ± 10 minutes
Class JIS C 1731 : 1997 Class 0.2
Maximum Circuit Voltage 6900 V
Withstand Voltage 16000 V
Rated Frequency 50 ~ 60 Hz
Approx. External Dimension 349 x 267 x 152 mm
Approx. External Weight 11 kg

Features

  • Precision conversion of electrical quantities on AC large-current or high-voltage circuits
  • Secondary circuit is isolated from primary circuit.
  • Capable of wide-range measurement using numerous ranges
    ModelDescription
    2243 00Current, 0.5/0.75/1/1.5/2/ 3/5/7.5/10/15/20/30/50/75/100A, 5A, ± 0.1%, ± 5 minutes, 2000 V, 343 x 256 x 136 mm
    2241 00Current, 10/15/30/50/100/ 250/300/500/750/1500A, 5A, ± 0.2%, ± 10 minutes, 10000 V, 318 x 246 x 128 mm
    2242 00Current, 10/15/30/50/100/ 250/300/500/750/1500A, 5A, ± 0.2%, ± 10 minutes, 16000 V, 349 x 267 x 152 mm
    2262 00Voltage, 3300/6600V, 110V, ± 0.2%, ± 10 minutes, 16000 V, 294 x 240 x 200 mm
    2261 01Voltage, 220/440/2200/3300V, 110V, ± 0.2%, ± 10 minutes, 10000 V, 255 x 240 x 200 mm
    Brochures

    Looking for more information on our people, technology and solutions?


    Contact Us
    Top
    live chat service provider