DIGITAL INSULATION TESTER MY40

  • Digital model with 4 voltage/resistance ratings
  • Multifunction
    Insulation resistance, AC voltage and conductor resistance measurement
    Insulation test mode: Comparator, memory, auto-hold and discharge functions
    All test modes: Live-line alarm (excluding AC voltage measurement), battery check and automatic power-off
  • Easy-to-view, fluctuation-free display
  • Double-action safety mechanism
  • Weight including main unit and batteries only, excluding accessories

Get a Quote
Ask an Expert

See more images:

 
 

Specifications - MY40 Digital Insulation Tester

Width 125 mm
Height 103 mm
Depth 53 mm
Display 3 1/2-digit LCD; 4000 count; backlight-illuminated; logarithmic bar graph; extension bar graph-no fluctuations, as the display shows the digits of a reading in the order in which each digit settles.
Comparator Function The MY40 alerts you by turning on the LOW symbol and sounding the buzzer if the measured value is smaller than the reference value. You can allocate as many as three user-defined reference values to each rating. The factory-set defaults are 0.1 MΩ, 0.2 MΩ and 0.4 MΩ.
Memory Function For each rating, you can save as many as 20 measurements at desired memory address numbers.
Automatic Discharge Function The MY40 automatically begins discharge when you turn off the MEAS switch. You can monitor the state of discharge by checking the bar graph and make sure discharge is complete by checking that the segment bar disappear.
High-Voltage Indicators The high-voltage symbol and LED lamp come on to alert you when the MY40 is in insulation testing mode or if any voltage remains to be discharged.
Live-Line Alarm If you apply an AC voltage of approximately 40 V or higher across the input terminals, the MY40 alerts you by blinking the LED lamp and sounding the buzzer.
Overrange Input Alarm If the voltage being measured exceeds 600 V during AC voltage measurement, the MY40 alerts you by flashing the Maximum Value indicator and sounding the buzzer.
Auto-Hold Function The tester retains the measured resistance for approximately 5 seconds after the MEAS switch is turned off.
Batteries Four AA (R6P) batteries
Weight 420 g
Ambient Temperature/Humidity Ranges 23 ±5 /45-75% RH
Standard Accessories Batteries (Qty - 4)
Earth Probe (98002) (Qty - 1)
Line Probe (98001) (Qty - 1)
Protection Cover (93013) (Qty - 1)
Shoulder Strap (99005) (Qty - 1)
User's manual (Qty - 1)

 

Tolerance Mentioned Conditions

Max. Deviation from Zero Scale Value 6 digits
Indication of mark on bar graph Approx. 4000 MΩ min. (500 V/1000 V)
Approx. 400 MΩ min. (125 V/250 V)
No-Load Voltage 130% max. of rated voltage
Rated Measuring Current 1 mA (0 to 20%) when in first effective measuring range
Max. Short-circuit Current 2 mA

 

Testing Performance

Model Rating Range Option Resolution Measuring Range Tolerance Lower Limit of measured Ω Rated Current Central Scale Value
MY40-01 125V/200MΩ 0.4000 0.1kΩ 0-0.0199MΩ ± (5%of rdg+6dgt) 0.125MΩ 1mA 5MΩ
4.000 1kΩ 0.0200-20.00MΩ* ± (2%of rdg+6dgt)
40.00 10kΩ 20.01-200.0MΩ ± 5%of rdg
200.0 100kΩ    
250V/200MΩ 0.4000 0.1kΩ 0-0.0499MΩ ±(5%of rdg+6dgt) 0.25MΩ 1mA 5MΩ
4.000 1kΩ 0.0500-20.00MΩ* ± (2%of rdg+6dgt)
40.00 10kΩ 20.01-200.0MΩ ±5%of rdg
200.0 100kΩ    
500V/2000MΩ 4.000 1kΩ 0-0.999MΩ ± (5%of rdg+6dgt) 0.5MΩ 1mA 50MΩ
40.00 10kΩ 1.000-500MΩ* ± (2%of rdg+6dgt)
400.0 100kΩ 501-2000MΩ ± 5%of rdg
2000 1MΩ    
1000V/2000MΩ 4.000 1kΩ 0-1.999MΩ ± (5%of rdg+6dgt) 2MΩ 0.5mA 50MΩ
40.00 10kΩ 2.000-1000MΩ* ± (2%of rdg+6dgt)
400.0 100kΩ 1001-2000MΩ ± 5%of rdg
2000 1MΩ    
Name Description File Type  
Product Manual   pdf icon
198 KB
Download
Insulation Tester Accessories   pdf icon
76 KB
Download
Insulation Tester Glossary   pdf icon
33 KB
Download
MY40 Users Manual *Please refer to the Supplements for the changes. pdf icon
358 KB
Download
Supplements (MY40 Users Manual)   pdf icon
641 KB
Download
Bulletin MY-E   pdf icon
727 KB
Download
 

All Products Guide
All Products Guide
PDF (10.26 MB)
CALL TOLL-FREE AT
1-800-888-6400
(8:00 TO 17:00 EASTERN)
y-Link