EY200 DIGITAL EARTH TESTER

  • Capable to measure by 3-pole or 2-pole method
  • Easy to measure with one touch button and dedicated test lead
  • Small and lightweight
  • Dust and drip proof (designed to IEC60529 IP54)

 
 

3-Pole Earth Resistance Measurement (Precise Measurement)

Connect the earth/ground electrode (E) and auxiliary spikes (P, C) to the main body using the accessory test lead. Put apart 5 to 10 m between E and P, and P and C, respectively. E, P, and C should be approximately in a line.

EY200 1

2-Pole Earth Resistance Measurement (simplified measurement)

A simplified 2-pole measuring method can be used if there is an almost perfectly earth/ground object such as a lead or iron water-pipe (plastic pipes cannot be used) or if there is an object with a known value of earth resistance, near the measurement site.

EY200 2

Name Model
Digital Earth Tester
EY200
EY200 General Specifications
Display
LCD Digital Display: 1999-count digital reading
Measuring Range
Earth Resistance: 2000Ω LSD: 0.01 to 1Ω
Earth Voltage: 200V
Accuracy
Earth Resistance: 20Ω range: ±2%rdg±0.1Ω
                             200Ω range: ±2%rdg±3dgt
                             2000Ω range: ±2%rdg3dgt
Earth Voltage:      ±1%rdg±4dgt
Measuring Frequency
Approx. 820Hz
Measuring Current
Approx. 3mA (at 20Ω range)
Battery Life
Approx. 4.5hours (at 5 second measuring 3300 times)
Operating Temp. and Humidity
0~40°C, 85%Rh or less
Dimensions
Approx. 105x158x70mm
Weight
Approx. 550g
Standard Accessories 3-pole Test Lead (Model 98074)
Earth Spikes (for EY200) (Model 98070)
2-pole Test Lead Set (Model 98075)
Soft Case (Model 93041)
Shoulder Belt (for EY200) (Model 99018)
Six AA (R6) dry cells
User's Manual

Name Description File Type  
LF EY200-EN EY200 Digital Earth Tester pdf icon
469 KB
Download
BU MY-E Insulation Testers Earth Testers pdf icon
850 KB
Download
 

All Products Guide
All Products Guide
PDF (8.40 MB)