Earth Tester EY200 (Digital)

What is an earth-ground tester/ground resistance tester?

EY200 is an earth resistance tester for testing power distribution lines, in-house wiring system, electrical appliances etc. The earth resistance tester by Yokogawa also has an earth voltage range for earth voltage measurement.

EY 200 Digital Earth Meter Features:

  • Designed to safety standard IEC 61557
  • Reference to IEC 60529: Degrees of protection provided by enclosures (IP54). Measurement can be made even under adverse weather conditions
  • Large, easy-to-read LCD digital display
  • 2P Test leads (for simplified measurement) has a structure that both the safety alligator clip and the test probe are available
  • Warns when earth resistance of auxiliary earth spikes exceeds the permissible limit
  • Convenient carrying soft bag for accessories etc.
  • 3-Pole Earth Resistance Measurement (Precise Measurement)

Connect the earth/ground electrode (E) and auxiliary spikes (P, C) to the main body using the accessory test lead. Put apart 5 to 10 m between E and P, and P and C, respectively. E, P, and C should be approximately in a line.

How to Measure Earthing Voltage

  • 3-Pole Earth Resistance Value Measurement (Precise Measurement)

Connect the earth/ground electrode (E) and auxiliary spikes (P, C) to the main body using the accessory test lead. Put apart 5 to 10 m between E and P, and P and C, respectively. E, P, and C should be approximately in a line.

EY200 1

 

  • 2-Pole Earth Resistance Value Measurement (Simplified Measurement)

A simplified 2-pole measuring method can be used if there is an almost perfectly earth/ground object such as a lead or iron water-pipe (plastic pipes cannot be used) or if there is an object with a known value of earth resistance, near the measurement site.

EY200 2

 

Name Model
Digital Earth Tester EY200
Display LCD Digital Display: 1999-count digital reading
Measuring Range Earth Resistance: 2000Ω LSD: 0.01 to 1Ω
Earth Voltage: 200V
Accuracy Earth Resistance:
20Ω range: ±2%rdg±0.1Ω
200 Ω range: ±2%rdg±3dgt
2000 Ω range: ±2%rdg3dgt
Earth Voltage: ±1%rdg±4dgt
Measuring Frequency Approx. 820Hz
Measuring Current Approx. 3mA (at 20Ω range)
Battery Life Approx. 4.5hours (at 5 second measuring 3300 times)
Operating Temp. and Humidity 0~40°C, 85%Rh or less
Dimensions Approx. 105x158x70mm
Weight Approx. 550g
Standard Accessories 3-pole Test Lead (Model 98074)
Earth Spikes (for EY200) (Model 98070)
2-pole Test Lead Set (Model 98075)
Soft Case (Model 93041)
Shoulder Belt (for EY200) (Model 99018)
Six AA (R6) dry cells