Features
3-Pole Earth Resistance Measurement (Precise Measurement)
Connect the earth/ground electrode (E) and auxiliary spikes (P, C) to the main body using the accessory test lead. Put apart 5 to 10 m between E and P, and P and C, respectively. E, P, and C should be approximately in a line.

2-Pole Earth Resistance Measurement (simplified measurement)
A simplified 2-pole measuring method can be used if there is an almost perfectly earth/ground object such as a lead or iron water-pipe (plastic pipes cannot be used) or if there is an object with a known value of earth resistance, near the measurement site.

Specifications
| Name | Model |
| Digital Earth Tester |
EY200 |
| EY200 General Specifications |
|
| Display |
LCD Digital Display: 1999-count digital reading |
| Measuring Range |
Earth Resistance: 2000Ω LSD: 0.01 to 1Ω Earth Voltage: 200V |
| Accuracy |
Earth Resistance: 20Ω range: ±2%rdg±0.1Ω 200Ω range: ±2%rdg±3dgt 2000Ω range: ±2%rdg3dgt Earth Voltage: ±1%rdg±4dgt |
| Measuring Frequency |
Approx. 820Hz |
| Measuring Current |
Approx. 3mA (at 20Ω range) |
| Battery Life |
Approx. 4.5hours (at 5 second measuring 3300 times) |
| Operating Temp. and Humidity |
0~40°C, 85%Rh or less |
| Dimensions |
Approx. 105x158x70mm |
| Weight |
Approx. 550g |
| Standard Accessories | 3-pole Test Lead (Model 98074) Earth Spikes (for EY200) (Model 98070) 2-pole Test Lead Set (Model 98075) Soft Case (Model 93041) Shoulder Belt (for EY200) (Model 99018) Six AA (R6) dry cells User's Manual |