With convenient sleep and data hold functions, LCD display, and a two-second response, the CL 235 Clamp-On AC/DC tester measures AC/DC voltage, resistance, and frequency measurements 33mm in diameter of the measurable conductor.
| Description | True RMS ACA, ACV, DCA, DCV |
|---|---|
| Method of detection | True RMS |
| Display | LCD (Digital display: 3999 counts) |
| DC Current Range | 400/1000A |
| DC Current Resolution | 0.1A |
| Response Time | Approx. 2 second |
| Range Switching | Auto-range |
| Data hold | On all range |
| Operating temperature and humidity | 0 - 40°C, 90% RH or less (no condensation) |
| Influence of conductor position | ±2% or less |
| Safety Standard | Conforms EN61010-1, EN61010-2-031, EN61010-2-032 |
| Circuit voltage | 600 Vrms or less |
| Withstanding voltage | 5.55 kV AC for one minute |
| Power Supply | 6F22 (006P) 9V x 1 6LR61 x 1 |
| Battery Life | Approx. 15 hours (continuous) |
| Consumed current | Approx. 15 mA |
| Sleep Function | Automatically powered down in about 30 minutes after the last switch operation |
| Diameter of measurable conductor | 33 mm at maximum |
| Dimensions | Approx. 91 (W) x 210 (H) x 40 (D) mm |
| Weight | Approx. 450 g |
| Accessories | Batteries, carrying case (93032) User's manual (IM CL235) |
| Peak Hold | On AC/DC current range, AC/DC voltage range |
| AC Current Range | 400/600A |
|---|---|
| AC Current Resolution | 0.1A |
| AC Current Frequency characteristics | 40~1kHz |
| AC Current Method of detection | True RMS |
| AC Voltage Measurement | O |
| DC Voltage Measurement | O |
| Continuity Check Measurement | O |
| Frequency Measurement | O |
| Temperature Measurement | - |
| Recorder output Function | - |
| Waveform monitor output Function | - |
| Data hold Function | O |
| Auto hold Function | - |
| Peak Hold Function | O |
| Maximum value memory Function | - |
| Mean value display Function | O |
| Filter Function | - |
| Range Hold Function | - |
| Auto ZERO Adjust Function | O |
| Auto power-off Function | Δ |
At 23°C±5°C,75%RH or less
Accuracy: ±( % rdg + dgt) = ±(% readout + value of least significant digit)
| Parameter | Reference | Accuracy |
|---|---|---|
| AC current | 400/600A | 1.5+5 (50/60Hz) |
| 3.5+5 (40~1kHz) | ||
| DC current | 400/1000A | 1.0+5 |
| AC voltage | 40/400/600V | 1.5+5 (50/60Hz) |
| 3.5+5 (40~1kHz) | ||
| DC voltage | 40/400/600V | 1.0+5 |
| Crest factor | ≦3 | |
| Resistance | 400/4000Ω | 1.0+5 , Beeps at below 20Ω (continuity check) |
| Frequency | 10~3000Hz | 1.5+5 |