Analog Insulation Tester 2406E Series (Multi Range) (DISCONTINUED)

Notice: This product was discontinued on Feb 28, 2018. See this replacement product:

The 2406E Analog Insulation Tester:

  • Analog models with two and three rating
  • AC voltage measurement
  • Automatic discharge
  • Sky blue EL backlight
  • Increased safety (covered battery charger)

Specifications - Model 240631

Rating 125V/20M~
25V/5M~
50V/10M~
Effective Measuring Range 0.001-5M~
0.005-10M~
0.01-20M~
Central Scale Value 0.1M~
0.2M~
0.5M~
AC Voltage Measurement 0 to 300 V
Lower Limit 0.025M~
0.05M~
0.125~
Rated Current 1 mA
Approx. Outer Scale Length 88 mm
Discharge Function The tester automatically begins discharge when you turn off the MEAS switch. The pointer swings if there is any residual voltage in the circuit under test. You can make sure discharge is complete by checking that the pointer swings back to the infinite (&
Approx. Width 120 mm
Approx. Height 110 mm
Approx. Depth 60 mm
Approx. Weight 500 g
Batteries Six AA (R6P) batteries
Standard Accessories Batteries (Qty- 6)
Carrying case (B9075MU) (Qty -1) Earth probe (blake); approx. 1 m long
Earth probes and Line Probes (98007) (Qty - 1)
User's Manual (Qty - 1)- With probe-housing pocket and neck strap

 

Standard Test Conditions - Model 240631

 

Ambient Temperature/Humidity Ranges 23 ±5 /45-75% RH
Position of Use Horizontal (5º max. of angle of inclination)
External Magnetic Fields None Battery voltage: Within effective voltage range (The pointer must stay within the range indicated by the BAT symbol when the battery check is performed.)
Tolerance Mentioned Conditions Resistance measurement: First effective measuring range = ±5% of reading
Second effective measuring range = ±10% of reading
Infinite and zero scale values: 0.7% max. of scale length
AC voltage: ±10% of maximum scale value
No-load voltage: 130% max. of rated voltage
Rated measuring current: 1 mA (0 to 20%) when in first effective measuring range
Short-circuit current: 12 mA max.

 

Specifications - Model 240641

 

Rating 125V/20M~
25V/5M~
50V/10M~
Effective Measuring Range 0.001-5M~
0.005-10M~
0.01-20M~
Central Scale Value 0.1M~
0.2M~
0.5M~
AC Voltage Measurement 0 to 300 V
Lower Limit 0.025M~
0.05M~
0.125~
Rated Current 1 mA
Approx. Outer Scale Length 88 mm
Discharge Function The tester automatically begins discharge when you turn off the MEAS switch. The pointer swings if there is any residual voltage in the circuit under test. You can make sure discharge is complete by checking that the pointer swings back to the infinite (&
Approx. Width 120 mm
Approx. Height 110 mm
Approx. Depth 60 mm
Approx. Weight 500 g
Batteries Six AA (R6P) batteries
Standard Accessories Batteries (Qty- 6)
Carrying case (B9075MU) (Qty -1) Earth probe (blake); approx. 1 m long
Earth probes and Line Probes (98007) (Qty - 1)
User's Manual (Qty - 1)- With probe-housing pocket and neck strap

 

Standard Test Conditions - Model 240641

 

Ambient Temperature/Humidity Ranges 23 ±5 /45-75% RH
Position of Use Horizontal (5º max. of angle of inclination)
External Magnetic Fields None Battery voltage: Within effective voltage range (The pointer must stay within the range indicated by the BAT symbol when the battery check is performed.)
Tolerance Mentioned Conditions Resistance measurement: First effective measuring range = ±5% of reading
Second effective measuring range = ±10% of reading
Infinite and zero scale values: 0.7% max. of scale length
AC voltage: ±10% of maximum scale value
No-load voltage: 130% max. of rated voltage
Rated measuring current: 1 mA (0 to 20%) when in first effective measuring range
Short-circuit current: 12 mA max.

 

Specifications - Model 240632

 

Rating 125V/20M~
Effective Measuring Range 0.01-20M~
Central Scale Value 0.5M~
AC Voltage Measurement 0 to 300 V
Lower Limit 0.125~
Rated Current 1 mA
Approx. Outer Scale Length 88 mm
Discharge Function The tester automatically begins discharge when you turn off the MEAS switch. The pointer swings if there is any residual voltage in the circuit under test. You can make sure discharge is complete by checking that the pointer swings back to the infinite (&
Approx. Width 120 mm
Approx. Height 110 mm
Approx. Depth 60 mm
Approx. Weight 500 g
Batteries Six AA (R6P) batteries
Standard Accessories Batteries (Qty- 6)
Carrying case (B9075MU) (Qty -1) Earth probe (blake); approx. 1 m long
Earth probes and Line Probes (98007) (Qty - 1)
User's Manual (Qty - 1)- With probe-housing pocket and neck strap

 

Standard Test Condtions - Model 240632

 

Ambient Temperature/Humidity Ranges 23 ±5 /45-75% RH
Position of Use Horizontal (5º max. of angle of inclination)
External Magnetic Fields None Battery voltage: Within effective voltage range (The pointer must stay within the range indicated by the BAT symbol when the battery check is performed.)
Tolerance Mentioned Conditions Resistance measurement: First effective measuring range = ±5% of reading
Second effective measuring range = ±10% of reading
Infinite and zero scale values: 0.7% max. of scale length
AC voltage: ±10% of maximum scale value
No-load voltage: 130% max. of rated voltage
Rated measuring current: 1 mA (0 to 20%) when in first effective measuring range
Short-circuit current: 12 mA max.

 

Specifications - Model 240642

 

Rating 250V/50M~
Effective Measuring Range 0.01-50M~
Central Scale Value 1M~
AC Voltage Measurement 0 to 300 V
Lower Limit 0.25~
Rated Current 1 mA
Approx. Outer Scale Length 88 mm
Discharge Function The tester automatically begins discharge when you turn off the MEAS switch. The pointer swings if there is any residual voltage in the circuit under test. You can make sure discharge is complete by checking that the pointer swings back to the infinite (&
Approx. Width 120 mm
Approx. Height 110 mm
Approx. Depth 60 mm
Approx. Weight 500 g
Batteries Six AA (R6P) batteries
Standard Accessories Batteries (Qty- 6)
Carrying case (B9075MU) (Qty -1) Earth probe (blake); approx. 1 m long
Earth probes and Line Probes (98007) (Qty - 1)
User's Manual (Qty - 1)- With probe-housing pocket and neck strap

 

Standard Test Conditions - Model 240642

 

Ambient Temperature/Humidity Ranges 23 ±5 /45-75% RH
Position of Use Horizontal (5º max. of angle of inclination)
External Magnetic Fields None Battery voltage: Within effective voltage range (The pointer must stay within the range indicated by the BAT symbol when the battery check is performed.)
Tolerance Mentioned Conditions Resistance measurement: First effective measuring range = ±5% of reading
Second effective measuring range = ±10% of reading
Infinite and zero scale values: 0.7% max. of scale length
AC voltage: ±10% of maximum scale value
No-load voltage: 130% max. of rated voltage
Rated measuring current: 1 mA (0 to 20%) when in first effective measuring range
Short-circuit current: 12 mA max.

 

Specifications - Model 240633

 

Rating 125V/20M~
250V/50M~
500V/100M~
Effective Measuring Range 0.01-20M~
0.01-50M~
0.05-100M~
Central Scale Value 0.5M~
1M~
2M~
AC Voltage Measurement 0 to 600 V
Lower Limit 0.125M~
0.25M~
0.5~
Rated Current 1 mA
Approx. Outer Scale Length 88 mm
Discharge Function The tester automatically begins discharge when you turn off the MEAS switch. The pointer swings if there is any residual voltage in the circuit under test. You can make sure discharge is complete by checking that the pointer swings back to the infinite (&
Approx. Width 120 mm
Approx. Height 110 mm
Approx. Depth 60 mm
Approx. Weight 500 g
Batteries Six AA (R6P) batteries
Standard Accessories Batteries (Qty- 6)
Carrying case (B9075MU) (Qty -1) Earth probe (blake); approx. 1 m long
Earth probes and Line Probes (98007) (Qty - 1)
User's Manual (Qty - 1)- With probe-housing pocket and neck strap

 

Standard Test Conditions - Model 240633

 

Ambient Temperature/Humidity Ranges 23 ±5 /45-75% RH
Position of Use Horizontal (5º max. of angle of inclination)
External Magnetic Fields None Battery voltage: Within effective voltage range (The pointer must stay within the range indicated by the BAT symbol when the battery check is performed.)
Tolerance Mentioned Conditions Resistance measurement: First effective measuring range = ±5% of reading
Second effective measuring range = ±10% of reading
Infinite and zero scale values: 0.7% max. of scale length
AC voltage: ±10% of maximum scale value
No-load voltage: 130% max. of rated voltage
Rated measuring current: 1 mA (0 to 20%) when in first effective measuring range
Short-circuit current: 12 mA max.

 

Specifications - Model 240343

 

Rating 125V/20M~
250V/50M~
500V/100M~
Effective Measuring Range 0.01-20M~
0.01-50M~
0.05-100M~
Central Scale Value 0.5M~
1M~
2M~
AC Voltage Measurement 0 to 600 V
Lower Limit 0.125M~
0.25M~
0.5~
Rated Current 1 mA
Approx. Outer Scale Length 88 mm
Discharge Function The tester automatically begins discharge when you turn off the MEAS switch. The pointer swings if there is any residual voltage in the circuit under test. You can make sure discharge is complete by checking that the pointer swings back to the infinite (&
Approx. Width 120 mm
Approx. Height 110 mm
Approx. Depth 60 mm
Approx. Weight 500 g
Batteries Six AA (R6P) batteries
Standard Accessories Batteries (Qty- 6)
Carrying case (B9075MU) (Qty -1) Earth probe (blake); approx. 1 m long
Earth probes and Line Probes (98007) (Qty - 1)
User's Manual (Qty - 1)- With probe-housing pocket and neck strap

 

Standard Test Conditions - Model 240643

 

Ambient Temperature/Humidity Ranges 23 ±5 /45-75% RH
Position of Use Horizontal (5º max. of angle of inclination)
External Magnetic Fields None Battery voltage: Within effective voltage range (The pointer must stay within the range indicated by the BAT symbol when the battery check is performed.)
Tolerance Mentioned Conditions Resistance measurement: First effective measuring range = ±5% of reading
Second effective measuring range = ±10% of reading
Infinite and zero scale values: 0.7% max. of scale length
AC voltage: ±10% of maximum scale value
No-load voltage: 130% max. of rated voltage
Rated measuring current: 1 mA (0 to 20%) when in first effective measuring range
Short-circuit current: 12 mA max.

 

Specifications - Model 240634

 

Rating 1000V/2000M~
250V/50M~
500V/100M~
Effective Measuring Range 0.01-50M~
0.05-100M~
1-2000M~
Central Scale Value 1M~
2M~
50M~
AC Voltage Measurement 0 to 600 V
Lower Limit 0.25M~
0.5M~
1~
Rated Current 1 mA
Approx. Outer Scale Length 88 mm
Discharge Function The tester automatically begins discharge when you turn off the MEAS switch. The pointer swings if there is any residual voltage in the circuit under test. You can make sure discharge is complete by checking that the pointer swings back to the infinite (&
Approx. Width 120 mm
Approx. Height 110 mm
Approx. Depth 60 mm
Approx. Weight 500 g
Batteries Six AA (R6P) batteries
Standard Accessories Batteries (Qty- 6)
Carrying case (B9075MU) (Qty -1) Earth probe (blake); approx. 1 m long
Earth probes and Line Probes (98007) (Qty - 1)
User's Manual (Qty - 1)- With probe-housing pocket and neck strap

 

Standard Test Condtions - Model 240634

 

Ambient Temperature/Humidity Ranges 23 ±5 /45-75% RH
Position of Use Horizontal (5º max. of angle of inclination)
External Magnetic Fields None Battery voltage: Within effective voltage range (The pointer must stay within the range indicated by the BAT symbol when the battery check is performed.)
Tolerance Mentioned Conditions Resistance measurement: First effective measuring range = ±5% of reading
Second effective measuring range = ±10% of reading
Infinite and zero scale values: 0.7% max. of scale length
AC voltage: ±10% of maximum scale value
No-load voltage: 130% max. of rated voltage
Rated measuring current: 1 mA (0 to 20%) when in first effective measuring range
Short-circuit current: 12 mA max.

 

Specifications - 240644

 

Rating 1000V/2000M~
250V/50M~
500V/100M~
Effective Measuring Range 0.01-50M~
0.05-100M~
1-2000M~
Central Scale Value 1M~
2M~
50M~
AC Voltage Measurement 0 to 600 V
Lower Limit 0.25M~
0.5M~
1~
Rated Current 1 mA
Approx. Outer Scale Length 88 mm
Discharge Function The tester automatically begins discharge when you turn off the MEAS switch. The pointer swings if there is any residual voltage in the circuit under test. You can make sure discharge is complete by checking that the pointer swings back to the infinite (&
Approx. Width 120 mm
Approx. Height 110 mm
Approx. Depth 60 mm
Approx. Weight 500 g
Batteries Six AA (R6P) batteries
Standard Accessories Batteries (Qty- 6)
Carrying case (B9075MU) (Qty -1) Earth probe (blake); approx. 1 m long
Earth probes and Line Probes (98007) (Qty - 1)
User's Manual (Qty - 1)- With probe-housing pocket and neck strap

 

Standard Test Conditions - Model 240644

 

Ambient Temperature/Humidity Ranges 23 ±5 /45-75% RH
Position of Use Horizontal (5º max. of angle of inclination)
External Magnetic Fields None Battery voltage: Within effective voltage range (The pointer must stay within the range indicated by the BAT symbol when the battery check is performed.)
Tolerance Mentioned Conditions Resistance measurement: First effective measuring range = ±5% of reading
Second effective measuring range = ±10% of reading
Infinite and zero scale values: 0.7% max. of scale length
AC voltage: ±10% of maximum scale value
No-load voltage: 130% max. of rated voltage
Rated measuring current: 1 mA (0 to 20%) when in first effective measuring range
Short-circuit current: 12 mA max.

 

Specifications - Model 240635

 

Rating 1000V/2000M~
250V/500M~
500V/1000M~
Effective Measuring Range 0.1-500M~
0.5-1000M~
1-2000M~
Central Scale Value 10M~
20M~
50M~
AC Voltage Measurement 0 to 600 V
Lower Limit 0.25M~
0.5M~
1~
Rated Current 1 mA
Approx. Outer Scale Length 88 mm
Discharge Function The tester automatically begins discharge when you turn off the MEAS switch. The pointer swings if there is any residual voltage in the circuit under test. You can make sure discharge is complete by checking that the pointer swings back to the infinite (&
Approx. Width 120 mm
Approx. Height 110 mm
Approx. Depth 60 mm
Approx. Weight 500 g
Batteries Six AA (R6P) batteries
Standard Accessories Batteries (Qty- 6)
Carrying case (B9075MU) (Qty -1) Earth probe (blake); approx. 1 m long
Earth probes and Line Probes (98007) (Qty - 1)
User's Manual (Qty - 1)- With probe-housing pocket and neck strap

 

Standard Test Conditions - Model 240635

 

Ambient Temperature/Humidity Ranges 23 ±5 /45-75% RH
Position of Use Horizontal (5º max. of angle of inclination)
External Magnetic Fields None Battery voltage: Within effective voltage range (The pointer must stay within the range indicated by the BAT symbol when the battery check is performed.)
Tolerance Mentioned Conditions Resistance measurement: First effective measuring range = ±5% of reading
Second effective measuring range = ±10% of reading
Infinite and zero scale values: 0.7% max. of scale length
AC voltage: ±10% of maximum scale value
No-load voltage: 130% max. of rated voltage
Rated measuring current: 1 mA (0 to 20%) when in first effective measuring range
Short-circuit current: 12 mA max.

 

Specifications - Model 240645

 

Rating 1000V/2000M~
250V/500M~
500V/1000M~
Effective Measuring Range 0.1-500M~
0.5-1000M~
1-2000M~
Central Scale Value 10M~
20M~
50M~
AC Voltage Measurement 0 to 600 V
Lower Limit 0.25M~
0.5M~
1~
Rated Current 1 mA
Approx. Outer Scale Length 88 mm
Discharge Function The tester automatically begins discharge when you turn off the MEAS switch. The pointer swings if there is any residual voltage in the circuit under test. You can make sure discharge is complete by checking that the pointer swings back to the infinite (&
Approx. Width 120 mm
Approx. Height 110 mm
Approx. Depth 60 mm
Approx. Weight 500 g
Batteries Six AA (R6P) batteries
Standard Accessories Batteries (Qty- 6)
Carrying case (B9075MU) (Qty -1) Earth probe (blake); approx. 1 m long
Earth probes and Line Probes (98007) (Qty - 1)
User's Manual (Qty - 1)- With probe-housing pocket and neck strap

 

Standard Test Conditions - Model 240645

 

Ambient Temperature/Humidity Ranges 23 ±5 /45-75% RH
Position of Use Horizontal (5º max. of angle of inclination)
External Magnetic Fields None Battery voltage: Within effective voltage range (The pointer must stay within the range indicated by the BAT symbol when the battery check is performed.)
Tolerance Mentioned Conditions Resistance measurement: First effective measuring range = ±5% of reading
Second effective measuring range = ±10% of reading Infinite and zero scale values: 0.7% max. of scale length
AC voltage: ±10% of maximum scale value
No-load voltage: 130% max. of rated voltage
Rated measuring current: 1 mA (0 to 20%) when in first effective measuring range
Short-circuit current: 12 mA max.
Model Rating Effective
Measuring range
Central
Scale Value
AC Voltage
Measuring range
Lower limit of
measured Ω*1
Rated Current
240631
25 V/5 MΩ
50 V/10 MΩ
125 V/20 MΩ
0.001 to 5 MΩ
0.005 to 10 MΩ
0.01 to 20 MΩ
0.1 MΩ
0.2 MΩ
0.5 MΩ
0 to 300 V
0.025 MΩ
0.05 MΩ
0.125 MΩ
1 mA
1 mA
1 mA
240641
240632
125 V/20 MΩ
250 V/50 MΩ
0.01 to 20 MΩ
0.01 to 50 MΩ
0.5 MΩ
1 MΩ
0 to 300 V
0.125 MΩ
0.25 MΩ
1 mA
1 mA
240642
240633
125 V/20 MΩ
250 V/50 MΩ
500 V/100 MΩ
0.01 to 20 MΩ
0.01 to 50 MΩ
0.05 to 100 MΩ
0.5 MΩ
1 MΩ
2 MΩ
0 to 600 V
0.125 MΩ
0.25 MΩ
0.5 MΩ
1 mA
1 mA
1 mA
240643
240634
250 V/50 MΩ
500 V/100 MΩ
1000 V/2000 MΩ
0.01 to 50 MΩ
0.05 to 100 MΩ
1 to 2000 MΩ
1 MΩ
2 MΩ
50 MΩ
0 to 600 V
0.25 MΩ
0.5 MΩ
1 MΩ
1 mA
1 mA
1 mA*2
240644
240635
250 V/500 MΩ
500 V/1000 MΩ
1000 V/2000 MΩ
0.1 to 500 MΩ
0.5 to 1000 MΩ
1 to 2000 MΩ
10 MΩ
20 MΩ
50 MΩ
0 to 600 V
0.25 MΩ
0.5 MΩ
1 MΩ
1 mA*2
1 mA*2
1 mA*2
240645
EL-Back-Light   Non-Back-Light *1 The minimum value at which the rated voltage can be maintained;
*2 0.55 mA in the case of the first effective measuring range

Looking for more information on our people, technology and solutions?


Contact Us

Precision Making

Top