Earth Tester EY200 (Digital)

What is an earth-ground tester/ground resistance tester?

EY200 is an earth resistance tester for testing power distribution lines, in-house wiring system, electrical appliances etc. The earth resistance tester by Yokogawa also has an earth voltage range for earth voltage measurement.

EY 200 Digital Earth Meter Features:

  • Designed to safety standard IEC 61557
  • Reference to IEC 60529: Degrees of protection provided by enclosures (IP54). Measurement can be made even under adverse weather conditions
  • Large, easy-to-read LCD digital display
  • 2P Test leads (for simplified measurement) has a structure that both the safety alligator clip and the test probe are available
  • Warns when earth resistance of auxiliary earth spikes exceeds the permissible limit
  • Convenient carrying soft bag for accessories etc.
  • 3-Pole Earth Resistance Measurement (Precise Measurement)

Connect the earth/ground electrode (E) and auxiliary spikes (P, C) to the main body using the accessory test lead. Put apart 5 to 10 m between E and P, and P and C, respectively. E, P, and C should be approximately in a line.

How to Measure Earthing Voltage

  • 3-Pole Earth Resistance Value Measurement (Precise Measurement)

Connect the earth/ground electrode (E) and auxiliary spikes (P, C) to the main body using the accessory test lead. Put apart 5 to 10 m between E and P, and P and C, respectively. E, P, and C should be approximately in a line.

EY200 1

 

  • 2-Pole Earth Resistance Value Measurement (Simplified Measurement)

A simplified 2-pole measuring method can be used if there is an almost perfectly earth/ground object such as a lead or iron water-pipe (plastic pipes cannot be used) or if there is an object with a known value of earth resistance, near the measurement site.

EY200 2

 

Name Model
Digital Earth Tester EY200
Display LCD Digital Display: 1999-count digital reading
Measuring Range Earth Resistance: 2000Ω LSD: 0.01 to 1Ω
Earth Voltage: 200V
Accuracy Earth Resistance:
20Ω range: ±2%rdg±0.1Ω
200 Ω range: ±2%rdg±3dgt
2000 Ω range: ±2%rdg3dgt
Earth Voltage: ±1%rdg±4dgt
Measuring Frequency Approx. 820Hz
Measuring Current Approx. 3mA (at 20Ω range)
Battery Life Approx. 4.5hours (at 5 second measuring 3300 times)
Operating Temp. and Humidity 0~40°C, 85%Rh or less
Dimensions Approx. 105x158x70mm
Weight Approx. 550g
Standard Accessories 3-pole Test Lead (Model 98074)
Earth Spikes (for EY200) (Model 98070)
2-pole Test Lead Set (Model 98075)
Soft Case (Model 93041)
Shoulder Belt (for EY200) (Model 99018)
Six AA (R6) dry cells
User's Manual

99018 Shoulder strap

For hanging the main body during measurement

Instruction Manuals
Drawings

Looking for more information on our people, technology and solutions?


Contact Us

Precision Making

Top